HID VertX V300 Output Control Interface

HID VertX V300 Output Control Interface - Output Control Processing for up to 12 Devices

HID

The HID VertX Products provide a complete and fully featured hardware/firmware infrastructure for biometric access control software host systems.

The HID VertX V300 Output control Interface connects 12 latching Form-C relays, which can connect up to 12 devices controllable by simple contact closures, such as logic inputs for process equipment, HVAC and elevator control panels, CCTV Switchers, etc. Loads exceeding 2 A @ 30 VDC should be controlled via interposing relays.

The HID VertX V300 features on-board flash memory, allowing program updates to be downloaded via the network. The HID VertX V300 connects to the HID V1000 through a high speed RS-485 network.

The HID VertX V1000 communicates with the system host via industry standard TCP/IP protocol over 10/100 Mbps Ethernet or the Internet. This architecture minimizes the impact on corporate LANs, by using only one TCP/IP address for every 32 Interfaces, and by handling low-level transactions on the RS-485 network.

Key Benefits :
  • Off-normal status programmable for each input point (NO or NC alarm devices may be used).
  • 12 latching Form-C relays, contacts rated at 2A @ 30VDC.
  • Connects to the V1000 via RS-485.
  • Reports all activity to the V1000.
  • Allows complex input/output linking when used with the V1000 and V200.
  • Attractive polycarbonate enclosure protects components from damage.
  • All connections and indicators are fully identified by silk-screened nomenclature on the cover.
  • UL 294 and UL 1076 recognized components.

Technical Specification :

Dimensions: 5.8"W x 4.825"H x 1.275" D (147.32 mm x 122.55 mm x 32.38 mm)
Weight: 13.6 oz (0.38 kg)
Power Supply Requirements: 60 mA @ 9-18 VDC (with no readers connected) Recommended: Supervised linear power supply with battery backup, input surge protection, and AC fail and battery low contact outputs. Seperate supervised, DC supply battery back-up recommended for relay activated devices.
Cable Distance:
RS-485: 4000 feet (1220 m) to host, using Belden 3105A, 22AWG twisted pair, shielded 100? cable
Output Cirbuits: 500 feet (150 m), 2-conductor, shielded, using ALPHA 1292C (22AWG) or Alpha 2421C (18AWG)

Frequently Asked Questions – HID VertX V300

What is the HID VertX V300?

HID VertX V300 is an output control interface module that connects 12 latching Form-C relays to the VertX V1000 via RS-485. It can control up to 12 devices using simple contact closures, including HVAC systems, elevator control panels, and CCTV switchers.

How does VertX V300 connect to the access control system?

V300 connects to the VertX V1000 via a high-speed RS-485 network up to 4,000 feet (1,220 m). The V1000 communicates with the host over TCP/IP, using only one IP address per 32 interface modules to minimise LAN overhead.

What loads can VertX V300 relays control?

V300 relays are rated at 2A @ 30V DC. Loads exceeding this rating should be controlled via interposing relays. The module is UL 294 and UL 1076 recognised.